GB/T 19413-2003
Unitary air conditioners for computer and data processing rooms
计算机和数据处理机房用单元式空气调节机
📚 References & Relations / 引用与关联
normative_reference
GB 17625.
normative_reference
GB 4208
normative_reference
GB 4343
normative_reference
GB 4343.
normative_reference
GB 4706.
normative_reference
GB 5226.
normative_reference
GB 8624
normative_reference
GB 9237
normative_reference
GB/T 14295
normative_reference
GB/T 17758-1999
normative_reference
GB/T 7778
normative_reference
GEC 61000-3-2
normative_reference
IEC 335-1
normative_reference
IEC 335-2-40
normative_reference
IEC 529
normative_reference
IEC 60204
normative_reference
ISO 5149
normative_reference
ISPR 14
normative_reference
ISPR 14-2
normative_reference
JB 8655
normative_reference
JB 8701
normative_reference
JB/T 12218
normative_reference
JB/T 4330
normative_reference
JB/T 4750
📖 Terms & Definitions / 术语和定义 ai_extracted
- 总制冷f
- total (sensible plus latent) cooling capacity 在规定的制冷量试验条件下,空调机从机房除去的显热和潜热之和,单位为瓦(W)o
- 制冷消耗功率refrigerating
- consumed power 在规定的制冷量试验条件下,空调机所消耗的总功率,单位为瓦(W)o
- 能效比(EER)
- energy efficiency ratio 总制冷量与制冷消耗功率之比。
- 显热制冷f
- sensible cooling capacity 在规定的制冷量试验条件下,空调机从机房除去的显热部分的热量,单位为瓦(W)e
- 显热比
- sensibl e heat ratio 显热制冷量与总制冷量之比,用等于1或小于1的小数表示。
- 冷风比
- cooling-air ratio 在规定的制冷量试验条件下,空调机的总制冷量与每小时送风量之比。单位为W/ (m'.h-').
- 乙二醉(或水)干式冷却器glycol
- (water) drycooler 由室外空气对管内带有排热量的乙二醉溶液(或水)进行冷却的冷却器。被冷却的乙二醇溶液(水) 可以用于制冷系统冷凝器的冷却介质,或者冬季采用乙二醇自然循环冷却器用于冷却机房内的循环 空气。
- 乙二醇(或水)自然循环节能冷却器glycol
- (water) free cooling fluid economi zer cycle cooler 在冬季室外温度较低时,关闭制冷系统,由在管内的乙二醇溶液(或水)冷却机房内循环空气的冷却 器,并达到节能效果。 3. 10 冷水盘管式water-cooling coil 采用中央空调冷水机组提供的冷水制冷并具有机房用空调机功能的机组。 3. 11 自然冷却 free cooling 在室外温度较低时,直接引人室外空气(部分或全部)对机房进行冷却的过程。 3. 12 制冷剂再加热系统 refrigerant reheat system 将压缩机排出的高温高压制冷剂气体送至再加热盘管,以制冷剂显热和潜热的热量进行送风温度 控制,并达到节能效果。 3. 13 综合部分负荷性能系数IPLV coeffici ent of integrated part load value 在规定工况下(见表7),按附录A所述方法计算出的部分负荷性能系数的值。 GB/T 1